OVER HEAD , BARE HARD DRAWN STRANDED ALUMINUM CONDUCTOR REINFORCED WITH STEEL CORE (ACSR)
ALUMINUM CONDUCTOR STEEL REINFORCED (ACSR)
GERMAN SIZES
ALUMINUM CONDUCTORS STEEL REINFORCED TO DIN 48204
B) Specification : DIN 48204
Area |
|
Stranding and wire diameter |
|
Weight |
|
|
Rating |
Nominal |
Al. |
Steel |
Total |
Equivalent copper area |
Overall diameter |
Al |
Steel |
Total |
Nominal breaking load |
Max. D.C. resistance at 20 °C |
Al |
Steel |
|
Al |
Steel |
|
|
|
Temp. amp |
Tropical amp |
mm2 |
mm2 |
mm2 |
mm2 |
mm2 |
mm2 |
mm |
mm |
mm |
kg/km |
kg/km |
kg/km |
kp |
ohm/km |
16 |
2.5 |
15.3 |
2.6 |
17.9 |
9.6 |
6/1.80 |
1/1.80 |
5.4 |
42 |
20 |
62 |
595 |
1.875 |
85 |
58 |
25 |
4 |
23.8 |
4 |
27.8 |
17.5 |
6/2.25 |
1/2.25 |
6.8 |
65 |
32 |
97 |
920 |
1.206 |
114 |
74 |
35 |
6 |
34.3 |
5.7 |
40 |
21.6 |
6/2.70 |
1/2.70 |
8.1 |
94 |
46 |
140 |
1265 |
0.8365 |
140 |
89 |
44 |
32 |
44 |
31.7 |
75.7 |
27.7 |
14/2.00 |
7/2.40 |
11.2 |
122 |
250 |
372 |
4500 |
0.657 |
170 |
100 |
50 |
8 |
48.3 |
8 |
56.3 |
30.4 |
6/3.20 |
1/3.20 |
9.6 |
132 |
64 |
196 |
1710 |
0.5941 |
172 |
105 |
50 |
30 |
51.2 |
29.8 |
81 |
32.2 |
12/2.33 |
7/2.33 |
11.7 |
141 |
237 |
378 |
4380 |
0.5642 |
187 |
109 |
70 |
12 |
69.9 |
11.4 |
81.3 |
44 |
26/1.85 |
7/1.44 |
11.7 |
193 |
91 |
284 |
2680 |
0.413 |
217 |
127 |
|